Specifications
-
Flow Range: 0.75 to 600 sfps [0.21 to 172 nmps]
(Air at standard conditions of 70º F and 14.7 psia [0ºC and 1013,25 mBar(a)].)
-
Accuracy : (at calibrated conditions)
Flow: ± 1% reading + 0.5% full scale.
Temperature: ± 2º F [± 1º C]
-
Temperature Coefficient:
With optional temperature compensation. Valid from 10% to 100% of full-scale calibration
Flow: Maximum ± 0.015% of reading/ºF up to 850ºF [±0.03% of reading/ºC up to 454 ºC]
-
Repeatability:
Flow: ± 0.5% reading
Temperature: ± 1º F [± 0.6º C]
-
Turndown Ratio: Factory set and field adjustable from 10:1 to 100:1 within the calibrated flow range.
-
Temperature Compensation:
Standard: ± 30º F [± -1º C]
Optional: ± 100º F [± 38º C]
-
Agency Approvals: FM, ATEX, IEC, CSA, CRN, GOST/RTN, NEPSI, CPA, PED, CE Mark (system approvals)
-
Calibration: N.I.S.T. Certified and Traceable Test Lab Calibration
-
MTBF (calculated): 110 Years
Flow Element
-
Materials of Construction: All welded 316L stainless steel or Hastelloy C for all wetted surfaces.
-
Process Connection:
Standard: 0.75 or 1 inch male NPT stainless steel compression fitting with adjustable Teflon ferrule rated up to 150 psig [10 bar (g)] and 200ºF [93ºC], or metal ferrule rated up to 250 psig [17 bar (g)] and 350ºF [177ºC].
Optional: Thread-on ANSI or DIN flanges, or retractable sensing element.
-
Insertion Lengths (Field Adjustable):2
1 to 6 inches [25 to 152 mm]
1 to 12 inches [25 to 305 mm]
1 to 21 inches [25 to 533 mm]
Customer specified fixed lengths are available. Consult FCI.
-
Operating Temperature (Process):
Standard: -40º to +350º F [-40º to +177º C]
Optional high temp: -100º to +500º F [-73º to +260º C];
Optional ultra-high temp: -100º to +850º F [-73º to +454º C];
-
Operating Pressure: To 250 psig [17 bar(g)]; de-rated with Teflon ferrule.
Flow Transmitter
-
Operating Temperature: 0º to 140º F [-18º to +60º C]
-
Input Power (Field Selectable): 85 to 265 Vac, 22 to 30 Vdc; 7 watts max; 230mA max.
-
Outputs:
Analog output: 4 to 20 mA, 1-5Vdc, 0-5Vdc, or 0-10Vdc. user selectable.
(mA: 700 ohm max. load; output per NAMUR guideline NE 431, field selectable for high =21.6mA or low =3.75mA. Isolated from input power in AC powered mode only.) (Vdc 100K min. load.)
Digital Communications:
RS-232C Serial I/O standard.
Options: HART, full two-way; Profibus, DP, profile 3, certification #Z01212
-
Digital Display: Optional LCD, 2 lines by 16 characters per line. Indicates flow rate and process temperature or totalized flow (field selectable) with engineering units displayed.
-
Remote Configuration: Transmitter may be mounted up to 1000 ft. [350 m] from flow element.
-
Enclosure Options:
-
NEMA 4/IP66 rated carbon steel box, approved for installation in Nonincendive Class I, Div.2, Groups A,B,C,D and suitable for Class II, Div.2 Groups F, G; Class III, Div. 2.
-
NEMA 4X/IP66 rated aluminum box, approved for installation in Nonincendive Class I, Div.2, Groups A,B,C,D and suitable for Class II, Div.2 Groups F, G; Class III, Div. 2.
-
Hazardous location, Ex-type aluminum, approved for installation in Class I, Div.1, Groups B,C,D,E,F,G; ATEX II2, GD, Exd IIC, T4.
Other Options and Accessories
-
Model FC88: Field Programmer/Communicator. Hand-held plug-in interface used to perform instrument set-up, programming, and for trouble-shooting.
-
VORTAB® Flow Conditioners: For use in piping installations with inadequate straight run, inline or out-of-plane elbows, control valves or any other obstructing configurations to improve flow meter performance.
Note 2: After installation, stainless steel ferrule will be permanently fixed at the installed length. |